TSE – Three-state element

Block SymbolLicensing group: STANDARD
PIC

Function Description
The TSE block transforms the analog input u to a three-state signal ("up", "idle" and "down") according to the diagram below.

PIC

Input

u

Analog input of the block

double

Outputs

UP

The "up" signal

bool

DN

The "down" signal

bool

Parameters

ep

The input value u > ep results in UP = on and DN = off  1.0

double

en

The input value u < en results in UP = off and DN = off  -1.0

double

epoff

UP switch off value; if UP = on and u < epoff then UP = off  0.5

double

enoff

DN switch off value; if DN = on and u > enoff then DN = off  -0.5

double

2019 © REX Controls s.r.o., www.rexygen.com