RLY – Relay with hysteresis

Block SymbolLicensing group: STANDARD
PIC

Function Description
The RLY block transforms the input signal u to the output signal y according to the figure below.

PIC

Input

u

Analog input of the block

Double (F64)

Output

y

Analog output of the block

Double (F64)

Parameters

ep

The value u > ep causes y = ap ("On")  1.0

Double (F64)

en

The value u < en causes y = an ("Off")  -1.0

Double (F64)

ap

Output value y in the "On" state  1.0

Double (F64)

an

Output value y in the "Off" state  -1.0

Double (F64)

y0

Initial output value at start-up

Double (F64)

2022 © REX Controls s.r.o., www.rexygen.com